How to see the current of dry type transformer

24-01-22

How to see the current of dry type transformer

dry type transformer current calculation formula:

According to the calculation formula, dry-type transformer current: I = S/(root number 3 * U)0/0.4KV dry-type transformer rated current calculation primary side similar 0.058 * KVA (dry-type transformer volume, specification model 10kV/0.4kV) secondary side similar 1.44 * KVA (dry-type transformer volume, specification model 10kV/0.4kV) subtitle response to the following calculation 50KVA dry-type transformer low voltage side rated current: 50*1.44 = 72A to calculate the rated current on the low voltage side of 80KVA dry-type transformer: 80*1.44 = 115.2A to calculate the rated current on the low voltage side of 100KVA dry-type transformer: 100*1.44 = 144A or so is the requirement for the calculation of the current and the current of dry-type transformer that people have introduced in detail to everyone for reference. In fact, the application of dry-type transformer is the key and the advantages of dry-type transformer should be shown, promote the safe and stable operation of dry-type transformers.

The above is the common dry-type transformer current related calculation method and the main current calculation method for your reference